ICEA S-75-381 Type MP-GC Three-Conductor Mine Power Feeder Cable CPE Jacket 8kV

               Feichun ICEA S-75-381 Type MP-GC Three-Conductor Mine Power Feeder Cable CPE Jacket 8kV

Applications :

These cables are designed for connections between units of mine distribution systems, suitable for installed in duct, conduit or open air and for direct burial in wet and dry locations.

Standards :

ICEA S-75-381/NEMA WC 58

 

ASTM B-8

 

CAN/CSA-C22.2 No.96

Construction :

Conductor

Stranded annealed bare copper conductor.

Conductor Shield

Conducting layer.

Insulation

Ethylene Propylene Rubber (EPR).

Insulation Shield

Conducting layer + copper tape.

Ground Check Conductor

Copper conductor with a yellow polypropylene insulation.

Grounding Conductor

Tinned copper conductor.

Jacket

Chlorinated Polyethylene (CPE), black.

Options :

  • Other jacket materials such as CSP/PCP/NBR/PVC/TPU are available upon request.

Mechanical and Thermal Properties :

  • Minimum Bending Radius: 12×OD.

  • Maximum Conductor Operating Temperature: +90℃.

Dimensions and Weight :

Construction

No. of
Strands

Grounding
Conductor
Size

Ground
Check
Conductor
Size

Nominal Insulation
Thickness

Nominal Jacket
Thickness

Nominal Overall
Diameter

Nominal Weight

Ampacity

No. of cores
×AWG/kcmil

-

AWG/
kcmil

AWG/
kcmil

inch

mm

inch

mm

inch

mm

lbs/kft

kg/km

A

3×6

7

10

8

0.115

2.9

0.11

2.8

1.41

35.8

1175

1749

93

3×4

7

8

8

0.115

2.9

0.11

2.8

1.52

38.6

1608

2392

122

3×2

7

6

8

0.115

2.9

0.11

2.8

1.58

40.1

1919

2855

159

3×1

19

5

8

0.115

2.9

0.11

2.8

1.66

42.2

2507

3730

184

3×1/0

19

4

8

0.115

2.9

0.11

2.8

1.74

44.2

2660

3958

211

3×2/0

19

3

8

0.115

2.9

0.14

3.6

1.90

48.3

3257

4846

243

3×3/0

19

2

8

0.115

2.9

0.14

3.6

2.00

50.8

3432

5107

279

3×4/0

19

1

8

0.115

2.9

0.14

3.6

2.12

53.8

4382

6520

321

3×250

37

1/0

8

0.115

2.9

0.14

3.6

2.22

56.4

4965

7387

355

3×350

37

2/0

8

0.115

2.9

0.14

3.6

2.43

61.7

6484

9647

435

3×500

37

4/0

8

0.115

2.9

0.14

3.6

2.70

68.6

8857

13178

536

As underground and surface mines move toward higher power density, longer feeder distances, and stricter safety controls, medium-voltage feeder cables have become a critical part of modern mine power systems. Among them, the Type MP-GC Three-Conductor Mine Power Feeder Cable with CPE Jacket, rated 8kV to ICEA S-75-381, is widely specified for its electrical reliability, mechanical robustness, and grounding safety.

What Does “Type MP-GC 8kV Mine Power Feeder Cable” Mean?

The designation MP-GC refers to a Mine Power – Ground Check cable designed specifically for medium-voltage mine distribution systems.

  • MP (Mine Power): Intended for fixed or semi-fixed mine power feeders

  • GC (Ground Check): Includes a dedicated ground-check conductor for monitoring grounding integrity

  • 8kV Rating: Suitable for medium-voltage mine distribution networks

  • ICEA S-75-381 Compliance: Meets North American mining cable construction and performance standards

This cable is not a trailing cable. Instead, it is a power feeder used between substations, switchgear, transformers, and major mine loads.

Where Is Type MP-GC 8kV Cable Typically Used in Mining?

What Are the Main Application Scenarios?

  • Underground mine distribution feeders

  • Connections between:

    • Substations and switchgear

    • Switchgear and transformers

    • Transformers and fixed equipment

  • Surface mine power networks

  • Permanent or semi-permanent installations

It is not designed for continuous dragging, unlike trailing cables.


What Are the Best Installation Practices for MP-GC 8kV Cables?

How Should the Cable Be Installed Safely?

  • Respect the 12×OD minimum bending radius

  • Avoid sharp edges in ducts or trenches

  • Ensure proper termination and grounding of copper tape shields

  • Protect the jacket from mechanical damage during pulling

  • Use qualified medium-voltage terminations

Correct installation is essential to achieving the cable’s full service life.


Frequently Asked Questions (FAQ)

Is Type MP-GC suitable for direct burial in wet ground?

Yes. The CPE jacket and EPR insulation are designed for wet and dry burial conditions.


Can MP-GC cables be used for mobile mining equipment?

No. MP-GC is a power feeder cable, not a trailing or reeling cable.


Why is a ground-check conductor important in mining?

It allows continuous monitoring of grounding integrity, improving electrical safety and reducing shock risk.


Does MP-GC comply with international standards?

Yes. It complies with ICEA S-75-381 / NEMA WC 58, ASTM B-8, and CAN/CSA-C22.2 No.96.


Can alternative jacket materials be specified?

Yes. CSP, PCP, NBR, PVC, or TPU jackets can be provided upon request for special environments.


Why Choose Feichun Type MP-GC 8kV Mine Power Feeder Cable?

Feichun’s MP-GC cables offer:

  • Proven ICEA-compliant construction

  • High electrical reliability

  • Excellent mechanical protection

  • Flexible size range for mine distribution systems

  • Customisation options for specific mining conditions


Looking for the Right MP-GC 8kV Cable for Your Mine?

If you are planning a new mine power distribution project or upgrading an existing system, selecting the correct Type MP-GC 8kV Mine Power Feeder Cable is critical for safety, compliance, and long-term reliability.

👉 Contact Feichun’s technical team for sizing support, application advice, or customised mining cable solutions.