FG7H1OAR Kabel Fleksibel 3.6/6kV & 6/10kV untuk Peralatan Tegangan Menengah, Tunneling & Pertambangan Bawah Tanah IEC 60502-2, Flame Retardant

FG7H1OAR 3.6/6kV dan 6/10kV Kabel

APLIKASI
Kabel fleksibel untuk pasokan energi pada peralatan tegangan menengah (MV), digunakan di terowongan dan pertambangan bawah tanah. Cocok untuk penggunaan di dalam dan luar ruangan.

KARAKTERISTIK
Tegangan Nominal (Uo/U)

  • 3,6/6 kV

  • 6/10 kV

Tegangan Uji

  • 3,6/6 kV: 12,5 kV

  • 6/10 kV: 21 kV

Suhu Lingkungan

  • Tetap: -40°C hingga +80°C

  • Fleksibel: +5°C hingga +80°C

Suhu Maksimum Arus Hubung Singkat: +250°C

Radius Minimum Pembengkokan

  • Tetap: 6 x diameter keseluruhan

  • Fleksibel: 10 x diameter keseluruhan

KONSTRUKSI

  • Konduktor Fase: Tembaga timah kelas 5

  • Isolasi: HEPR (Hard Ethylene Propylene Rubber)

  • Lapisan Semi-Konduktif: Pita semi-konduktif di atas konduktor dan lapisan karet semi-konduktif dalam & luar pada isolasi

  • Konduktor Pengaman (PE): Anyaman kawat tembaga individual

  • Konduktor Kontrol: Tembaga timah kelas 5

  • Pengisi Pusat: Campuran karet pada penyangga tekstil poliester

  • Selubung Dalam: PVC (Polyvinyl Chloride)

  • Armour: Anyaman kawat baja di atas selubung dalam

  • Selubung Luar: PVC (Polyvinyl Chloride)

  • Warna Selubung: Merah

STANDAR
Umumnya sesuai IEC 60502-2, IEC 60228
Tahan Api sesuai IEC/EN 60332-1-2

DIMENSI

The FG7H1OAR flexible cable is rapidly gaining attention in industrial, tunneling, and underground mining sectors across Indonesia. Designed for medium-voltage (MV) equipment and applications exposed to mechanical stress, its flame-retardant properties and robust construction make it a trusted solution for reliable energy distribution in challenging environments.

What Are the Main Features of FG7H1OAR 3.6/6kV and 6/10kV Cables?

FG7H1OAR cables are designed for flexible energy supply to medium-voltage equipment, particularly in tunnels and underground mines. The main features include:

  • Voltage Ratings: 3.6/6kV and 6/10kV

  • Test Voltage: 12.5kV (3.6/6kV) and 21kV (6/10kV)

  • Temperature Range: Fixed: -40°C to +80°C, Flexed: +5°C to +80°C

  • Maximum Short-Circuit Temperature: +250°C

  • Minimum Bending Radius: Fixed: 6× overall diameter, Flexed: 10× overall diameter

  • Flame Retardant: Complies with IEC/EN 60332-1-2

The combination of mechanical resilience and flame-retardant properties ensures safety, reliability, and long service life in demanding environments.


What Are the Typical Applications of FG7H1OAR Cables?

FG7H1OAR cables are widely used in tunnels, underground mining, and medium-voltage distribution systems:

  1. Underground Mining: Powering heavy machinery such as drills, shovels, and conveyors.

  2. Tunneling Projects: Providing flexible energy distribution for tunnel boring machines (TBMs).

  3. Medium Voltage Equipment: Supply to switchgear, transformers, and industrial motors.

  4. Indoor and Outdoor Installations: Resistant to moisture, dust, and mechanical impact.

Real Indonesian Use Case: Grasberg Mine, Papua

In Papua’s Grasberg underground mine, FG7H1OAR 6/10kV cables were deployed to power tunneling machines under extreme mechanical stress. The steel wire braid armour protected the cable from abrasion against rock walls, while the PVC sheath allowed long-term exposure to high humidity without degradation.


How Does FG7H1OAR Compare with Other MV Mining Cables?

Feature

FG7H1OAR

Standard XLPE MV Cable

Reeling Cable

Voltage Range

3.6/6 & 6/10 kV

6/10 kV

3.6/6 kV

Flexibility

High

Medium

Very High

Flame Retardant

IEC 60332-1-2

IEC 60332

IEC 60332

Mechanical Protection

Steel wire braid

None or light armouring

Reinforced

Indoor/Outdoor

Yes

Limited outdoor

Limited outdoor

Ideal Use

Tunneling & underground mining

Fixed distribution

Mobile equipment

FG7H1OAR combines flexibility, mechanical protection, and flame retardancy, making it ideal for medium-voltage industrial environments with high mechanical stress.


Frequently Asked Questions (FAQ)

Can FG7H1OAR cables be used in open-pit mines?

Yes, the cables are suitable for outdoor applications, including open-pit mining. However, for extreme sunlight exposure, additional UV protection is recommended.

How does FG7H1OAR differ from standard XLPE MV cables?

FG7H1OAR uses HEPR insulation for superior flexibility and abrasion resistance, while standard XLPE cables are stiffer and less suited for bending-intensive applications.

What maintenance is required for FG7H1OAR in underground mining?

Routine inspection of the PVC sheath and steel wire armour is sufficient. Look for cuts, abrasions, or heat damage. Voltage drop monitoring is recommended for long cable runs.

Can these cables handle short-circuit events?

Yes. The maximum short-circuit temperature is +250°C. Correctly sized cables, according to cross-section and load, can safely handle short-circuit conditions.

What is the recommended bending radius for installation?

  • Fixed: 6× overall diameter

  • Flexed: 10× overall diameter

Are FG7H1OAR cables flame-retardant?

Yes. They comply with IEC/EN 60332-1-2, ensuring reduced fire propagation in case of an incident.


Why Choose FG7H1OAR for Your Project?

FG7H1OAR cables offer flexibility, durability, flame retardancy, and mechanical protection, making them the optimal choice for medium-voltage distribution in:

  • Underground mining operations

  • Tunneling projects

  • Industrial plants with mobile heavy equipment

By selecting FG7H1OAR, engineers can reduce downtime, maintenance costs, and safety risks.


For reliable, high-performance medium-voltage cable solutions, FG7H1OAR 3.6/6kV and 6/10kV flexible cables provide long-lasting safety and operational efficiency. Contact our team for:

  • Project-specific cable sizing

  • Technical consultations

  • Installation guidance and supply

Ensure your mining or tunneling project achieves maximum safety and energy efficiency today.