BS 7835 3.8/6.6kV LSZH Armoured Power Cable XLPE Insulated AWA/SWA Medium Voltage Cable for Direct Burial

BS 7835 3.8/6.6 kV Cable – General Information

Item

Description

Cable Standard

BS 7835

Voltage Rating Uo/U (Um)

3.8/6.6 (7.2) kV

Test Voltage (AC)

15 kV

Application

Armoured power distribution cables for external installations and direct burial in power networks

Sheath Colour

Red

UV Resistance

Yes


Temperature & Mechanical Characteristics

Parameter

Value

Maximum Operating Temperature

90 °C

Maximum Short Circuit Temperature

250 °C

Minimum Bending Radius – Single Core

15 × overall diameter

Minimum Bending Radius – Multi Core

12 × overall diameter

Reduced Bending Radius (near joint/termination)

Single core: 12 × OD / 3 core: 10 × OD (with controlled bending using a former)


Cable Construction

Component

Description

Conductor

Class 2 stranded compacted copper conductor

Conductor Screen

Semi-conductive XLPE

Insulation

XLPE (Cross-Linked Polyethylene)

Insulation Screen

Semi-conductive XLPE

Metallic Screen

Concentric copper wires and copper tape

Separator

Binding tape

Inner Sheath

LSZH (Low Smoke Zero Halogen)

Armour

Single core: AWA (Aluminium Wire Armour)
Multi core: SWA (Galvanised Steel Wire Armour)

Outer Sheath

LSZH (Low Smoke Zero Halogen)


Standards & Fire Performance

Requirement

Standard

Conductor Standard

IEC/EN 60228

Flame Retardant

IEC/EN 60332-1-2, IEC/EN 60332-3-24

Low Smoke

IEC/EN 61034-1 / 61034-2

Halogen Free

IEC/EN 60754-1 / 60754-2


Dimensions – Single & Multi Core Cables

Single Core

No. of Cores

Nominal CSA (mm²)

Nominal Overall Diameter (mm)

Nominal Weight (kg/km)

1

35

24.30

1,023

1

50

25.50

1,171

1

70

27.30

1,418

1

95

29.20

1,719

1

120

31.10

2,013

1

150

32.30

2,386

1

185

35.00

2,866

1

240

37.70

3,486

1

300

41.70

4,256

1

400

47.10

5,406

1

500

51.90

6,693

1

630

55.80

8,212

Three Core

No. of Cores

Nominal CSA (mm²)

Nominal Overall Diameter (mm)

Nominal Weight (kg/km)

3

50

48

4,500

3

70

52

5,500

3

95

56

6,500

3

120

60

7,500

3

150

63

8,500

3

185

67

10,000

3

240

74

13,000

3

300

80

15,500

3

400

89

19,000


Electrical Characteristics – Single Core

Installation conditions: In Ground at 20 °C / In Air at 30 °C

CSA (mm²)

Max DC Resistance @20 °C (Ω/km)

Inductance (mH/km) Flat / Trefoil

Capacitance (µF/km) Flat / Trefoil

Current Rating (A) In Ground Flat / Trefoil

Current Rating (A) In Air Flat / Trefoil

35

0.524

0.748 / 0.401

0.266

201 / 191

238 / 199

50

0.387

0.719 / 0.381

0.297

241 / 227

285 / 241

70

0.268

0.684 / 0.357

0.339

301 / 277

356 / 301

95

0.193

0.659 / 0.342

0.381

364 / 331

435 / 365

120

0.153

0.636 / 0.327

0.416

424 / 379

496 / 419

150

0.124

0.620 / 0.319

0.454

479 / 422

554 / 479

185

0.0991

0.602 / 0.310

0.495

549 / 476

637 / 543

240

0.0754

0.579 / 0.300

0.556

595 / 550

746 / 640

300

0.0601

0.562 / 0.295

0.617

626 / 591

831 / 722

400

0.0470

0.543 / 0.290

0.681

675 / 662

920 / 827

500

0.0366

0.525 / 0.283

0.758

748 / 744

1043 / 949

630

0.0283

0.507 / 0.276

0.853

981 / 856

1180 / 1076


Electrical Characteristics – Multi Core (3 Core)

CSA (mm²)

Max DC Resistance @20 °C (Ω/km)

Inductance (mH/km)

Capacitance (µF/km)

Current Rating (A) In Ground 20 °C

Current Rating (A) In Air 30 °C

50

0.387

0.33

0.30

208

196

70

0.268

0.31

0.35

255

249

95

0.193

0.29

0.39

307

307

120

0.153

0.28

0.43

353

353

150

0.124

0.28

0.47

396

406

185

0.0991

0.27

0.51

447

464

240

0.0754

0.26

0.55

523

548

300

0.0601

0.26

0.57

581

632

400

0.0470

0.26

0.59

653

726

When engineers, EPC contractors, and utility companies search for a medium voltage armoured cable for direct burial, the BS 7835 3.8/6.6kV LSZH Armoured Power Cable is often at the top of the list.
But what exactly is this cable, how is it constructed, and why is it widely specified in power networks across Southeast Asia, including Indonesia?

What Does BS 7835 Mean for a Medium Voltage Armoured Cable?

BS 7835 is a British Standard that specifies low smoke zero halogen (LSZH) power cables designed to reduce toxic gas emission, smoke density, and fire propagation.

For medium voltage (MV) applications, BS 7835 cables are chosen when:

  • Fire safety is critical

  • Underground or enclosed spaces are involved

  • Human safety and asset protection are priorities

This makes BS 7835 especially relevant for urban power networks, industrial plants, and infrastructure projects in Indonesia, where safety regulations are becoming stricter.


What Is the Structure of a BS 7835 3.8/6.6kV Armoured Cable?

The performance of this cable comes from its layered engineering design, optimized for mechanical strength, electrical reliability, and fire safety.

How Is the Conductor Designed?

  • Class 2 stranded compacted copper conductor

  • Offers low resistance, high current capacity, and mechanical robustness

  • Complies with IEC/EN 60228

Why Is XLPE Used for Insulation and Screens?

  • XLPE (Cross-Linked Polyethylene) insulation rated at 90°C

  • Semi-conductive XLPE screens ensure:

    • Uniform electric field

    • Reduced partial discharge risk

    • Stable long-term MV performance

What Role Does the Metallic Screen Play?

  • Concentric copper wires with copper tape

  • Provides:

    • Earth fault current path

    • Electromagnetic shielding

    • Improved system safety

Why Are LSZH Inner and Outer Sheaths Important?

  • Low Smoke Zero Halogen (LSZH) materials:

    • Minimal smoke generation

    • No corrosive halogen gases

  • Critical for substations, tunnels, power corridors, and industrial zones

What Is the Difference Between AWA and SWA Armour?

  • Single-core: AWA (Aluminium Wire Armour)
    → Avoids magnetic losses

  • Multi-core: SWA (Galvanised Steel Wire Armour)
    → Superior mechanical protection


What Are the Key Technical Specifications of BS 7835 3.8/6.6kV Cable?

What Are the Electrical Ratings?

  • Voltage rating (Uo/U/Um): 3.8/6.6 (7.2) kV

  • AC test voltage: 15 kV

  • Maximum conductor temperature:

    • Continuous: 90°C

    • Short circuit: 250°C

What Are the Bending Radius Requirements?

Cable Type

Minimum Bending Radius

Single core

15 × overall diameter

Multi core

12 × overall diameter

Near joints (controlled)

Reduced with formers

These limits are crucial during installation in Indonesian soil conditions, which often involve tight trenches.


Where Is BS 7835 3.8/6.6kV Armoured Cable Commonly Used?

Why Is It Suitable for Direct Burial?

  • Heavy-duty armour resists:

    • Soil pressure

    • Stones and backfill

    • Accidental excavation damage

  • LSZH sheath resists:

    • Moisture

    • UV exposure

    • Chemical contamination

Typical Applications in Indonesia

  • PLN distribution networks

  • Industrial estates (Java, Batam, Bekasi)

  • Cement plants and smelters

  • Power supply for oil & gas facilities

  • Substation interconnections


What Is a Real Indonesian Case Study Using BS 7835 Cable?

Industrial Power Upgrade in West Java

A manufacturing park in West Java upgraded its 6.6kV underground power network to meet new fire safety standards.

Why BS 7835 Was Selected:

  • Direct burial without concrete ducts

  • LSZH compliance for emergency evacuation routes

  • Long-term thermal stability

Results:

  • Reduced maintenance incidents

  • Improved safety audit scores

  • Lower insurance risk classification


Frequently Asked Questions (FAQ)

Is BS 7835 cable suitable for tropical climates like Indonesia?

Yes. XLPE insulation and LSZH sheath perform well under high humidity and temperature.

Can this cable be installed without ducts?

Yes. It is designed for direct burial.

Is BS 7835 mandatory in Indonesia?

Not mandatory, but increasingly specified in high-risk and high-value projects.

Single-core or three-core: which should I choose?

  • Single-core: Higher current, flexible layout

  • Three-core: Compact installation, simpler termination


What Should You Consider Before Selecting BS 7835 3.8/6.6kV Cable?

  • Load current and future expansion

  • Installation environment

  • Fire safety requirements

  • Soil conditions

  • Compliance with project specifications


If you are designing or upgrading a 6.6kV power system and need a reliable LSZH armoured cable for direct burial, BS 7835 3.8/6.6kV XLPE AWA/SWA cable is a proven solution.

👉 Contact a professional cable supplier for:

  • Cable sizing support

  • Technical datasheets

  • Project-specific recommendations

  • Compliance documentation

Choosing the right cable today ensures safety, reliability, and long-term performance for your power network.